This chapter describes the process of
locating the cause of malfunctions in electrical circuits
associated with hydraulic-control systems. The information
includes testing devices and types of grounding points. Also
addressed in this chapter are the safety measures personnel
should take when working on or around electrical circuits.
7-1. Hydraulics and Electricity.
Hydraulics and electricity are often compared because the systems
have similarities. A hydraulic circuit requires a power source
(usually a pump), a load device (actuator), and conductors. The
circuits differ mainly in the-
-
- An electrical circuit also
requires a power source (battery, generator), a
load device (light, bell, motor), and proper
connections. An assortment of devices also
controls, directs, and regulates the flow of
electrical current.
- Hydraulic and electrical
components are usually represented on diagrams by
their own set of standardized symbols. Electrical
diagrams are often called schematics. Figure 7-1
shows some of the more common symbols. Hydraulic
and electrical systems and circuits have many
differences. For example, electrical current is
invisible, hydraulic fluid is not; electrical
current flows through solid wires, hydraulic
fluid flows through hollow lines. Figure 7-2
shows symbols for electrical and hydraulic
components. Figure 7-3 compares a hydraulic
circuit and an electrical circuit.



7-2. Troubleshooting Electrical
Devices. Electrical troubleshooting is the process of
locating the cause of malfunctions in electrical circuits. The
following paragraphs contain some general troubleshooting
information as well as specific tests for determining the status
of some electrical devices. Skill in troubleshooting electrical
equipment and circuits requires-
-
- Following systematic steps that
narrow down the problem to a smaller area of the
equipment is much more efficient than
trial-and-error methods. The troubleshooting
procedure detailed below can be very useful in
organizing the problem-solving effort and
reducing equipment downtime:
- a. Procedure. The
following troubleshooting procedure consists of
five steps that you should perform in order.
These steps represent the most reliable method of
learning and applying a logical approach to
problem solving and can be applied to any
equipment, regardless of size.
- (1) Step One: Identify
the Symptom. A symptom is an external
indication that a circuit or device is
not functioning correctly. You can
identify a symptom by investigating the
problem by sight, sound, smell, and
touch. For example, visually inspecting
the equipment may reveal that a circuit
component has overheated and changed
color or that an indictor lamp which
should be on is not. A peculiar odor may
lead you to discover melted insulation,
or a chattering noise could indicate that
a solenoid is about to fail. Moving
controls or adjusting knobs may change
the problem or have no effect at all. The
fact that the equipment is not operating
is a symptom.
- If someone else was
operating the equipment when it failed,
ask the person if he noticed anything
unusual before it failed. Funny noises,
things that do not look quite right, and
improper operating sequences are symptoms
that could lead to the cause of the
problem. If you cannot find any
immediately identifiable symptoms, try
operating the equipment once you
determine that it is safe to do so. Watch
what works and what does not work. Note
anything that does not seem right, no
matter how small. Take the time to
conduct a thorough investigation.
- (2) Step Two: Analyze
the Symptom. In this step, you identify
the functions where symptoms indicate a
malfunction. Use the information you
obtained during your identification,
along with the schematic and functional
block diagrams and knowledge of how the
equipment is supposed to operate, to make
logical technical deductions. For
example, after careful examination, you
find that a clamp in a plastic-injection
molding machine will not pressurize.
Further analysis, without using test
equipment, narrows the problem to a clamp
that is closed, clamp pressurization, or
prefill shift, any of which might contain
the faulty circuit.
- (3) Step Three: Isolate
the Single Faulty Function. In this step,
you use test equipment to decide which
faulty function is actually causing the
malfunction. When making these tests, use
the following guidelines:
- For example, if taking
an ohmmeter reading can determine the
fault, do not take a voltmeter reading as
that requires power on the equipment. If
you must disassemble half of the machine
to reach a test point, perform a simpler
test first. Test at a midway point in the
circuitry, if possible. A good reading at
the midway point eliminates the preceding
functions and indicates that the problem
is in the remaining circuits. A faulty
signal at the midway point means that the
problem is in the functions that process
the signal before the midway point.
- In the injection molding
example, test the clamp's pressurization
circuits where the clamp's fully closed
signal input either eliminates that
function or confirms that the cause of
the problem is a clamp that is not fully
closed and, therefore, cannot be
pressurized. Continue testing inputs and
outputs of the suspect functions until
you identify and confirm the single
faulty function.
- (4) Step Four: Isolate
the Faulty Circuit. In this step, you
locate the single malfunctioning circuit
within a functional group of circuits.
Use the accumulated symptom and test data
to close in on the single faulty circuit.
Follow the guidelines from step three,
but apply them to the circuits related to
the faulty function. Use schematic and
block diagrams to locate test points.
- In the
injection-molding-machine example, assume
that the clamp's fully closed signal is
not present at the input to the clamp's
pressurization circuits. Test within the
clamp's closed circuits until you
identify a single faulty circuit. The
first test may reveal that the output of
the clamp's fully closed circuit is bad.
A check of the inputs to this circuit may
indicate that the input from a clamp's
closed-limit switch is bad but that all
others are good. You can now identify the
problem as being associated with one of
the relatively few parts contained in a
single circuit.
- (5) Step Five:
Locate/Verify the Cause of the
Malfunction. The tests you make in this
step identify the failing part within the
faulty circuit. Test the circuit until
you find the cause of the malfunction.
Examine and test the faulty part to
verify that it has caused the problem and
produced the observed symptoms.
- In checking out the
clamp's fully closed circuit, for
example, remove the suspected limit
switch from the circuit and test it with
an ohmmeter to determine if the switch's
contacts are closing correctly to
complete the circuit. Connect the
ohmmeter across the contacts of the
switch and actuate the switch's arm
several times while checking the meter
reading. If the contacts close properly,
the meter should read zero ohms when the
arm is in one position and infinity when
the arm is in the other position.
- If the meter pointer
does not move when the switch arm is
actuated, disassemble and examine the
switch. If this last examination reveals
that the mechanical linkage connecting
the switch's arm to the contacts is
broken, then you have found the cause of
the malfunction. A final analysis should
show that this cause explains the
observed symptoms. However, the procedure
is not complete until you verify the
findings. In this example, you would
install a new limit switch in the circuit
and operate the equipment to confirm that
you have fixed the problem.
- b. Testing Devices. The
following paragraphs outline some basic
electrical tests that you can conduct on specific
pieces of equipment that were discussed earlier.
As part of a troubleshooting test, you should
mechanically inspect these devices. Also, if
spare parts are available, substitute a good part
for a suspect part as a quick method of returning
the equipment to operation. Test the suspect part
and either repair it or discard it.
- (1) Potentiometer. Since
a potentiometer is a variable-resistance
device, it should be disconnected from
its circuit and tested with an ohmmeter,
if it is suspect. Only two of the three
leads need to be disconnected for this
test. Be very careful when adjusting
small potentiometers on printed circuit
boards. They are quite fragile and can
easily be broken if rotated beyond the
end stops. Test a potentiometer as
follows:
- (2) Solenoid Coil. If a
solenoid is thought to be faulty, do the
following:
- (3) Relay. Test a
suspect relay as follows:
- (4) Transformer. When
you determine, by voltage readings or
symptom information, that a transformer
may be the cause of a malfunction, check
the primary and the secondary coil
resistance with an ohmmeter. Disconnect
one end of the primary winding and one
end of the secondary winding from the
rest of the circuit before testing. If
the failure is the result of an open
winding, the ohmmeter will read infinity
when connected across the defective
winding. If the failure is caused by
shorted turns within a winding, the
problem is more difficult to diagnose
because the ohmmeter will indicate a very
low resistance. Since a winding consists
of a length of conductor wound into a
coil, the resistance readings are
normally quite low anyway. If you suspect
shorted turns-
- Be sure to adjust the
zero-ohms control before making the
measurement; hold the test probes by the
insulated portion only. You may have
difficulty determining if the reading is
accurate since the measurement is so
close to the low end of the ohms scale.
Compare the readings to a replacement
transformer's, if one is available. To
positively verify that the transformer is
faulty, you may have to substitute a good
transformer for the suspect one.
- (5) Diode. You can use a
simple resistance check with an ohmmeter
to test a diode's ability to pass current
in one direction only. To test a suspect
diode-
- A good diode should have
real low resistance when forward biased
and high resistance when reverse biased.
If the diode reads a high resistance in
both directions, it is probably open. If
the readings are low in both directions,
the diode is shorted. A defective diode
could show a difference in forward and
backward resistance. In this case, the
ratio of forward to backward resistance
is the important factor. The actual ratio
depends on the type of diode. As a rule
of thumb, a small signal diode should
have a ratio of several hundred to one. A
power rectifier can operate with a ratio
as low as ten to one.
7-3. Ground. Every
electrical circuit has a point of reference to which all circuit
voltages are compared. This reference point is called ground, and
circuit voltages are either positive or negative with respect to
ground. Connections to ground that are made for safety reasons
refer to earth ground. When voltage measurements are taken, the
difference of potential between a point in the circuit and a
ground point is measured by the voltmeter. This type of ground is
referred to as chassis or common ground.
- a. Earth Ground.
Initially, ground referred to the earth itself
and since has represented a point of zero
potential or zero volts. A short circuit within a
device that connects live voltage to the frame
could cause a serious shock to anyone touching
it. However, if the frame is connected to earth
ground, it is held at the safe potential of zero
volts, as the earth itself absorbs the voltage.
- Today, a third prong on grounded
power plugs connects most stationary equipment to
earth ground through the electrical wiring
system. Some equipment is connected to earth
ground by a conductor that goes from the metal
frame of the equipment to a long copper rod that
is driven into the earth. Some appliances are
often grounded by connecting the conductor to a
water pipe running into the ground. In any case,
the frames of all equipment connected to the
earth are at the same zero volt potential. This
prevents shocks that might occur should a person
touch two pieces of ungrounded equipment at the
same time.
- b. Chassis or Common Ground.
In some cases, electrical circuits used today are
not connected directly to earth ground; however,
they still require a point of reference or a
common point to which elements of each circuit
are connected. For example, a portable
battery-operated transistor radio does not have a
ground conductor connecting it with the earth. A
strip of conducting foil on the internal circuit
board is used as the common point. In an
automobile battery, the negative terminal is
generally connected to the engine block or
chassis frame by a heavy cable. The connecting
point, as well as every other point on the metal
frame, is considered to be a ground for the
electrical circuits of the vehicle. The rubber
tires insulate the vehicle from the earth ground.
In these examples, ground is simply a zero
reference point in an electrical circuit and is
referred to as chassis ground. All voltages in
the circuit are measured with respect to this
common point.
- c. Zero Reference Point. Without
a zero reference point, voltage could not be
expressed as a positive or negative value. The
schematic diagrams in Figure 7-4 illustrate this
point:
- d. Isolation Between Earth
and Chassis Ground. Industrial equipment
often requires an earth and a separate chassis
ground for proper operation. The earth ground
represents an actual potential of zero volts,
while the chassis ground is used only as a
reference point and may be at some potential
above or below the earth ground. In these cases,
the earth ground and the chassis ground are not
connected together at any point in the equipment.
However, during installation or repairs, the
chassis ground may be inadvertently connected to
the earth ground. To check for this condition,
use a 1.5-volt, D-cell battery and holder,
connecting wires, and a voltmeter. Make sure that
the equipment is OFF before making the test.
- In Figure 7-5, the battery is
installed between the chassis ground and the
earth ground. The voltmeter, set to measure 1.5
volts direct current (DC), is connected across
the battery. If a connection exists between the
chassis and the earth ground, it will place a
short circuit across the battery, and the
voltmeter will indicate zero volts. If this is
the case, temporarily disconnect one end of the
battery to keep it from discharging while looking
for the improper connection between the grounds.
When you find the connection, remove it and
reconnect the battery and the meter. The
voltmeter should read the battery potential of
1.5 volts. If the voltmeter reading is still zero
volts, an improper connection still exists in the
equipment. Repeat the test until the voltmeter
reads the battery voltage. Remember to disconnect
the battery after completing the test.
7-4. Safety. Effective
safety measures are a blend of common sense and the knowledge of
basic electrical and hydraulic principles and of how a system or
circuit operates, including any dangers associated with that
operation. General safety information and safety practices are
listed below. The list is not all inclusive, is not intended to
alter or replace currently established safety practices, and does
not include safety practices for hydraulic equipment.
- a. Information. When
working with electrical equipment, consider the
following information regarding safety:
- b. Practices. When
working with electrical equipment, consider the
following safety rules:
HOMEPAGE