CHAPTER 16
THREE-PHASE ALTERNATING CURRENT MOTORS
INTRODUCTION
Most of the power-generating systems, ashore and afloat,
produce AC. For this reason, a majority of the motors used
throughout the Army operate on AC. There are other advantages to
using AC. In general, AC motors are less expensive and easier to
maintain than DC machines.
An AC motor is particularly well suited for constant speed
operations. This is because its speed is determined by the
frequency of the power source and the number of poles constructed
in the motor.
Alternating current motors are built in different sizes,
shapes, and ratings for many different jobs (Figures
16-1 and 16-2). It is impossible to
address all forms of AC motors in this text. This chapter will
address only the squirrel cage induction motor.


INDUCTION MOTOR PRINCIPLE
The principle of the revolving magnetic field is the key to
the operation of the AC motor. Induction motors rely on revolving
magnetic fields in their stators (stationary windings) to cause
their rotors to turn. Stators themselves do not turn. Stators are
permanently attached to the inside of the motor housing in the
same manner that the stationary windings in the generator are
connected to the main frame. The revolving magnetic fields
created in the stator windings provide the necessary torque to
move the rotor.
The idea is simple. A magnetic field in a stator can be made
to appear to rotate electrically, around the inside periphery of
the motor housing. This is done by overlapping several different
stator windings. A magnetic field is developed in each different
stator winding at a different time. Just before the magnetic
field of one winding decays, the winding overlapping it develops
the same magnetic polarity. As this second magnetic field decays
in the second winding, another overlapping winding develops a
magnetic field of the same polarity, and the sequence repeats
itself. Successive stator windings develop magnetic fields in an
orderly procession and appear to progressively move around the
inside of the motor housing.
These individual magnetic fields are the property of current
flow in the motor stator. This current flow comes from the three
individual phase currents of the three-phase generator output. In
Chapter 14, Figure 14-8 shows the
three single-phase voltages/currents that develop in the
generator main armature completing individual circuits. Circuit
A-B in the generator armature has a like A-B winding in the
motor's stator. Each of the three circuit combinations (A-B, B-C,
and C-A) are developed independently in the generator over a
short period of time. The generator circuits are then completed
through the motor's stator windings in a similar manner. As long
as the current and magnetic field develops and decays in an
orderly, progressive manner around the periphery of the motor
frame, a revolving magnetic field exists.
A revolving magnetic field in the stator is only part of the
operation. Another magnetic field needs to be created in the
rotor so that the torque and rotation can develop using the
principles of magnetic attraction and repulsion. The magnetic
field developed in the rotor is a product of induction. As soon
as the stator and the rotor windings develop their magnetic
affiliation, torque will develop, and the rotor will turn.
REVOLVING FIELD OPERATION
The rotating field is set up by out-of-phase currents in the
stator windings. Figure 16-3 shows the
manner in which a rotating field is produced by stationary coils
or windings when they are supplied by a three-phase current
source. For the purpose of explanation, rotation of the field is
developed in the figure by "stopping" it at six
selected positions, or instants. These instants are marked off at
60-degree intervals on the sine waves representing currents in
the three phases A, B, and C.

At instant 1, the
current in phase B is maximum positive. (Assume plus 10 amperes
in this example.) Current is considered to be positive when it is
flowing out from a motor terminal. At the same time (instant 1), current flows into A and C
terminals at half value (minus 5 amperes each in this case).
These currents combine at the neutral (common connection) to
supply plus 10 amperes out through the B phase.
The resulting field at instant 1 is
established downward and to the right as shown by the arrow NS.
The major part of this field is produced by the B phase (full
strength at this time) and is aided by the adjacent phases A and
C (half strength). The weaker parts of the field are indicated by
the letters n ands. The field is a two-pole field extending
across the space that would normally contain the rotor.
At instant 2, the current in phase B is
reduced to half value (plus 5 amperes in this example). The
current in phase C has reversed its flow from minus 5 amperes to
plus 5 amperes, and the current in phase A has increased from
minus 5 amperes to minus 10 amperes.
The resulting field at instant 2 is now
established upward and to the right as shown by the arrow NS. The
major part of the field is produced by phase A (full strength)
and the weaker parts by phases B and C (half strength).
At instant 3, the current in phase C is
plus 10 amperes, and the field extends vertically upward. At instant 4 the current in phase B becomes
minus 10 amperes, and the field extends upward and to the left.
At instant 5, the current in phase A
becomes plus 10 amperes, and the field extends downward and to
the left. At instant 6, the current in
phase C is minus 10 amperes, and the field extends vertically
downward. In instant 7 (not shown), the current corresponds to
instant 1 when the field again extends downward and to the right.
Thus, a full rotation of the two-pole field has been done
through one full cycle of 360 electrical degrees of the
three-phase currents flowing through the stator windings.
SYNCHRONOUS SPEED
The number of poles in the motor will determine how many times
the magnetic field in the stator revolves for any given generated
frequency. The term "pole" should bring to mind the
terms used in Chapter 2 on magnetism. The
following definition of a motor pole gives it a practical
application value: A motor pole is the completed circuit of a
motor stator winding that, when energized by a current, will
produce a magnetic field concentration, or polarity.
The speed of the revolving stator field is called synchronous
speed. The synchronous speed depends on two factors:
-
- The number of poles.
-
- The frequency of the power source.
The synchronous speed, in turn, determines the speed of the
motor rotor. Just as with the generator prime mover speed, the
generated frequency and rotor speed are directly related. The
number of poles in the motor determines how fast the revolving
field will move around the inside periphery of the motor housing
at a given frequency. The more poles a motor has, the longer it
takes to energize all the sets of poles and the slower the motor
field will revolve at 60 hertz.
Table 16-1 shows the speed of the
revolving field (or synchronous speed) for a 60-hertz generated
power supply.

The direction of rotation of three-phase
machines are determined by the phase sequence. Normal phase
sequence on board Army vessels is A-B-C. This can be verified
from the switchboard. A set of lights indicates the phase
sequence from the power source.
As the generator rotates, current flow is
induced in the armature. Each phase in the armature becomes
electrically active. The order in which the phases become
electrically active determines the order in which the motor's
stator receives the current. The motor that receives current
A-B-C-A-B-C will rotate in a given direction. If any two leads
change places, then the two affected phases change their sequence
of arrival. If phases B and C are exchanged, then phase C will
follow phase A. This reverses the direction of the revolving
magnetic field in the stator. Current arrives at the motor
C-BA-C-B-A. When the revolving field in the motor's stator
changes direction, the motor's rotor changes direction. Reversing
the generator's output will turn the motor's rotor in the
opposite direction as well. If the generator's output is
reversed, then it is known as C-B-A phase sequence.
By reversing any two phase wires, either at
the generator's armature or the motor's terminals, the phase
sequence will change at that point. Reversing any two leads, at
the same point, will restore normal phase sequence. Industry
standard dictates configuration control by identifying the
conductors to be exchanged: the A and C phase for generators, P1
and P3 for feeders, L1 and L3 for branch circuits, or T1 and T3
for motor terminals.
Figure 16-4 shows a cutaway view of a
three-phase induction motor. There is very little difference
between the AC motor and the AC generator. The rotor is supported
by bearings at each end. The stator is freed in position to the
inside of the motor frame. The frame encloses all the components
of the motor.

Frame
The motor frame, among other considerations,
is a determining factor in the placement of the motor. Each motor
frame enclosure has certain characteristics and specific vessel
applications. There are seven basic types of enclosures:
Electric equipment exposed to the weather or
in a space where it is exposed to seas, splashing, or similar
conditions must be watertight or in a watertight enclosure.
Electric motors, however, must be either watertight or waterproof
(Code of Federal Regulations, Title
46, Subpart 111.01-9).
Stator Windings
The motor stator is the stationary winding bolted to the
inside of the motor housing. The stator windings have a very low
resistance. The three-phase AC generator armature is built very
similar to the three-phase AC motor stator. Each machine has the
stationary conductor winding insulated its entire length to
prevent turn-to-turn shorts. The winding is also insulated from
the frame. The motor stator winding is identical to a generator
armature that has a like amount of poles. Each winding is
overlapped and is electrically and mechanically 120 degrees out
of phase.
Figure 16-5 shows an end view of the
stationary windings. Each of the three-phase windings are divided
into many additional coils uniformly distributed throughout the
stator. This even distribution allows more effective use out of
the magnetic fields that will be developed within the stator
windings when current is present. This also produces a more even
torque (pulling and pushing by magnetic forces) for the rotor.

Rotor Windings
The rotor looks like a solid cylinder
supported at each end by bearings (Figure
16-6). Upon closer examination, you may see thin bars
embedded in the laminated cylinder at an angle almost parallel to
the rotor shaft. At each end of the cylindrical rotor core, there
are shorting rings. Each end of a bar is connected to the
shorting rings. These rotor windings are similar in construction
to the amortisseur or damper windings found in the generator.

Rotor Current
These short-circuited rotor bars become a
transformer secondary. The magnetic field established in the
stator induces an EMF in the rotor bars. The rotor bars and the
shorting rings complete a circuit, and a current flow is then
established in these rotor bars. Remember, whenever a current
flow is established so is a magnetic field. Since this magnetic
field is the property of induction and induction opposes that
which creates it, the magnetic field pole in the rotor is of the
opposite polarity of the stator field pole that generated it.
Magnetism principles apply, and the rotor's polarity is attracted
to the stator's opposite polarity. The revolving field of the
stator, in effect the revolving magnetic polarity, pulls and
pushes the initially established rotor field in the rotor. The
pulling and pushing produces torque, and the motor rotor turns.
Short-Circuited Rotor Bars
Words often used to describe the solid bar
windings found in the induction motor rotor are
"short-circuited bars." A short circuit is a very low
resistance situation that has very little restraint in reducing
current flow. A short circuit condition can have devastating
effects on the entire electrical environment. The rotor bars are
designed for very low resistance to obtain certain motor
operating characteristics. The rotor bars themselves are not
entirely the cause for the short circuit condition. The great
inrush of motor current is initiated because of the relative
motion between the stationary rotor winding and the revolving
stator field. This is part of the maximum current the motor will
draw initially from the distribution system. Through
transformer-like action, the great difference in relative motion
induces a large EMF and resulting current flow in the rotor.
The inrush will be dramatically reduced as
the rotor speed increases. The closer the rotor RPM is in
relation to the speed of the revolving stator magnetic field, the
less relative motion exists. Less relative motion means less
induced EMF and a reduction in rotor and stator winding currents.
Shortly after power is applied to the motor, the current is
reduced to as little as 10 percent. Once the motor is operating
at normal speed, the full-load current (FLC), stipulated on the
data plate, is maintained (Figure 16-7).
Large motors installed on Army watercraft can have an increase in
current 6 to 12 times greater than the data plate FLC rating.
Mechanically overloading a motor slows the rotor and increases
current. It is the increase in current, no matter how little,
that results in heating sufficient to destroy motors.

If the rotor could turn at synchronous
speed, then there would be no relative motion between the
magnetic field of the stator and the rotor conductor bars. This
would end the induction process in the rotor, and the rotor would
lose its magnetic field.
This is not possible with an induction
motor. If rotor speed equaled synchronous speed, the rotor would
stop. However, as soon as the rotor slowed, even slightly,
induced EMF and current would again flow in the rotor winding.
Rotor speed would be maintained somewhere below synchronous
speed. Slip is the difference between the synchronous speed and
the actual speed of the rotor. Slip is more often expressed as a
percentage:
Percent slip = (synchronous speed - rotor
speed) x 100
synchronous speed
Percent slip = (1,800 RPM - 1,785 RPM) x 100
1,800 RPM
Percent slip = 15 x 100
1,800
Percent slip = 0.8 percent
An induction motor will always have a
difference in speed between the rotor and the stator field.
Without this difference, there would be no relative motion
between the field and rotor and no induction or magnetic field in
the rotor.
Rotor and therefore motor speed is
determined by the number of poles, the frequency, and the
percentage of slip.
Induction motor rotors are designed to have
a specific amount of resistance. The resistance in the rotor
determines the comparative ease with which the magnetic field in
the rotor becomes established. The motor starting current, slip,
and torque are modified by the rotor resistance. By developing a
motor with a high rotor resistance, a larger slip is developed
because the magnetic field of the rotor cannot develop very
quickly. A step-by-step sequence of events portrays the actions
between the stator and rotor in a relatively high rotor
resistance induction motor:
However, extra torque does not come without
some complications. Increased torque means an increased current
demand on the distribution system. There is also an increase in
slip at full load. Higher resistance rotors are not acceptable
for all applications. This is the reason for the many rotor
designs.
The rotor resistances are identified by the
National Electrical Manufacturers Association (NEMA) and
designated by design.
The resistance of the stator windings is
very low. The less resistance a component has, the greater the
current from the generator. Motor current requirements can be,
among others, attributed simply to size. The larger the stator
winding diameter is, the larger the motor itself is constructed.
A motor, with its low resistance stator windings, initially
reacts as a short circuit. It is not until the expanding and
contracting magnetic fields cut the many turns of wire adjacent
to each conductor in the stator winding that the current is
further reduced. This momentary inrush of current, combined with
the transformer-like action, described in Short-Circuit Rotor
Bars, accounts for the overall current needed for a motor.
When the vessel is initially started, a
ship's electrical distribution system may have only lights in
operation. There is very little current registering on the
switchboard ammeters. This is because the resistance in the light
bulbs is so high. The high resistance keeps current down.
As soon as a motor is connected to the line,
the current draw becomes excessive. The ammeter will register
more than six times the normal operating current of the motor.
This is what happens: The motor's internal wiring is of
negligible resistance. Since all electrical components are
connected in parallel in the distribution system, the parallel
circuit rules apply. Resistance in a parallel circuit is always
less than the smallest resistor. (This is why the largest idle
motor is of considerable concern when designing a ship's
distribution system.) The motor wire resistance is now the only
determining factor for the generator's current output. The
current immediately supplied by the generator is called inrush
current. If the rotor is mechanically prevented from moving, the
current is then called locked rotor current.
Westinghouse developed a program to
investigate motor circuit protection. A power source and cabling
system was designed to handle LRC levels far in excess of that
normally found on Army watercraft. The objectives of the test was
to determine how much the fault current would exceed the normal
full-load current if a rotor was mechanically prevented from
rotating. Results show that lock rotor current progresses in
steps. Approximately 44 cycles after the initial LRC, LRC almost
doubled in value. This double LRC was maintained for an
additional 42 cycles until the LRC increased again. This time the
LRC was stepped up to three times initial LRC. The LRC continued
to increase in steps of similar values with fewer cycles between
steps. Test results hold little consolation in the knowledge that
at no time did the fault current exceed 50 times the FLC. The
test established that motor failures start at relatively low
values (6 x FLC) and cascade quickly in mere seconds. A current
draw of the observed magnitude would devastate the
current-producing capacity of the generating system and
effectively terminate the operation of the distribution system if
not interrupted rapidly. Remember, all improperly protected
circuits are fire hazards!
The induction motor poses many problems for
the electrical system environment. The motor's great current draw
can tax the electrical system to the extent that the generated
voltage will drop. (There is internal resistance in the
generator, too. The greater the current through the generator's
conductors, the greater the voltage dropped in the entire
electrical system, E = IR). When this generated voltage drops
below a certain point, relays, contractors, and other electrical
holding coils become de-energized, and their associated equipment
stops operating.
A complete understanding of motor operating
characteristics is necessary to understand the effects of the
motor on the electrical system and the requirements for
protecting a motor against overload conditions. The two most
prominent effects from the motor are --
Inductive Reactance
The discussion on transformers explained the
properties of induction on a coil of wire. Except for the minimal
resistance of the wire itself, there appears to be nothing to
prevent a power source from restricting the majority of its
current. As it turns out, induction opposes a change in current.
A back voltage or counter EMF (CEMF) is developed and pushes back
on the power supply. In the DC system, the CEMF restricts current
flow. In AC, the CEMF impedes current flow change. The AC system
with its various amplitudes and current directions creates a
generator out of any inductor. This shuttle power is
inductor-generated and must be overcome by the generator. When
the inductive reactance (shuttle power), the motor's load, and
assorted losses are overcome, the generator supplies only enough
additional current to keep the motor rotor turning. The only
problem exists with the inductive reactance. This generated CEMF
and its resulting current are there to be overcome. Inductive
reactance, therefore, is not consumed.
Whenever inductance is involved in the
electrical system, a lagging power factor results. The power
factor is extremely poor when the motor is first started. The
lower the power factor, the greater the increase in current
needed to operate the motor. A power factor of .5 can be expected
when a motor is first started. At the motor's rated speed, a
power factor of .8 is normal. Unity or 1.0 is the best use of
power. Not only does the generator have to supply current for
overcoming the wire resistance, but it must overcome the
inductive reactance from the motor itself.
Never select a motor that is overrated for
its application. Contrary to popular belief, when a motor is not
operated at its rated capacity, the electrical system efficiency
is decreased. The power factor is decreased, goes further away
from unity, and more power is required to operate the motor than
would have normally been required for a motor operating at the
designated rated capacity.
Never operate a motor above its rated
capacity. It will not operate long. Motors and generators can
easily operate at many times their normal current ratings for a
short period of time. Even so, excess heat is generated. If this
heat is not permitted to dissipate rapidly, insulation damage
will result.
High Rotor EMF
Inductive reactance is always an important
consideration when choosing motors for the electrical system. But
the induction motor has another characteristic that influences
the electrical environment even more. This is called the rotor
EMF.
The motor acts much like a transformer. The
stator winding becomes the primary winding, and the rotor becomes
the secondary winding. If the secondary winding of a transformer
becomes shorted out, the primary winding effectively becomes the
generating source. The primary winding, an extension of the
generator, provides as much current as possible according to the
Maximum Power Transfer Theorem.
At the instant when the rotor has not yet
begun to move and current is applied to the stator, there is a
maximum slip. There is maximum relative motion between the stator
and the rotor and a maximum induced voltage into the
low-resistance rotor bars. These rotor bars act like a short
circuit drawing very large currents from the source because there
is negligible resistance to restrict the current flow.
The stator windings have extremely large
currents because of the large induced rotor EMF. Both the rotor
and the stator develop maximum magnetic fields from maximum
current flows.
The rotor's magnetic field, from induction,
is of the opposite polarity of the stator's magnetic field. The
rotor starts to move. As the rotor speed increases, the relative
motion between the two windings decreases. The decreasing
relative motion decreases the EMF and the resulting current flow
in the rotor bars. The power source demand decreases as does the
current flow to the stator.
This phenomenon is readily observable by
using an induction ammeter and an AC motor. Simply place the jaws
of the ammeter around one insulated conduct or (not all). Start
the motor and observe the meter readings. The current will start
very high and then taper off quite rapidly as the motor increases
in speed.
Load Changes
Counter electromotive force developed in the
stator windings could restrict current flow to moderation, except
for the overwhelming EMF induced in the rotor. Many other factors
affect the operation of the motor, such as impedance, changes in
torque, and the angle in degrees separating the stator and rotor
magnetic fields. Table 16-2 is a
simple reference to the factors affecting a motor and the
electrical environment under three motor operations.

The following is a brief outline on the
motor-operating characteristics under several conditions:
Motor requirements for current vary widely
with the load. In addition, the current actually exceeds the
normal operating range when the motor is first started. How then
can the motor be protected against the excessive currents outside
the normal parameters of operation and still be protected from
small prolonged current increases?
Fuse Protection
Fuses have several disadvantages in
protecting the motor. If a fuse is used to protect the motor for
its full-load current rating, then the fuse would open during the
initial inrush of current. A fuse designed to pass inrush current
would not protect the motor against currents less than the inrush
but greater than the normal full-load current. For every 1C rise
over normal ambient temperature ratings for insulation, it has
been estimated that the life expectancy of a motor can be reduced
almost a year. Current generates heat in a motor. Heat destroys
the motor insulation.
Time-delay fuses have been used for motor
protection in the past. However, another problem develops when
using three fuses for the protection of the three-phase motor.
Should only one of the three fuses open when the motor was
operating, the motor would not stop immediately. It would
continue to operate. The operation of three-phase motors on only
two lines constitutes a single-phase condition. The three-phase
motor cannot operate single phasing for long without internal
damage. This would not become apparent until enough damage was
incurred that the motor would be irreparable. The fuse was not
the answer for protecting three-phase motors.
Magnetic Motor Starters
The magnetic motor starter is a magnetic
contactor with an overload protection device (Figure 16-8). Unlike the fuse, the magnetic
motor starter does not have to be replaced. It can be reset
repeatedly.

The Motor Circuits
Larger current-demanding motors use two
circuits for operation. One circuit is the three-phase power
circuit supplied from the distribution power panel. The other
electrical circuit is the control circuit.
Figure 16-9 shows the magnetic motor
starter and the power circuit from the distribution power panel.
The heavy, dark lines provide the three-phase, high
current-carrying power to the motor.
Inside the magnetic motor starter, directly
under the coil, are three large main contact sets. These contacts
are in series with the power panel A, B, and C phase terminals
and the T1, T2, and T3 motor terminals. As long as these contacts
are closed, current from the power distribution panel can operate
the motor. This is one circuit.
The other circuit controls the three large
contact sets explained above. The coil in Figure
16-9 actually moves the contacts. Figure
16-10 shows the control circuit that the coil is actually in.
M represents the coil in Figure 16-9.

The M coil is supplied single-phase power
from the magnetic motor starters A and B phase terminals (also
known as L1 and L2 terminals). Figure
16-10 shows two M coils: one in its true physical position in
the magnetic motor starter and the other in the line diagram to
explain its function electrically. There is actually only one M
coil. The same applies to the NC overload contacts.
When the START button is pressed, a complete circuit from A
phase through the M coil, through the NC overload contacts, to
the B phase is completed in the control circuit. The M coil
energizes and moves a bar, known as an armature, that is in
physical contact with the three large power contacts in the
motor's three-phase power circuit. Figure
16-11 illustrates this action.

The main power circuit contacts for the
motor are held open by spring tension (Figure
16-11 view A). When the coil becomes energized, the magnetic
attraction between the armature and the magnet overcomes spring
tension, and the main contacts for the motor close (Figure 16-11 view B). The motor now
operates.
When the current to the motor is too great, the overload
heaters get hot. The heaters are in series with the motor
terminals and the main contacts for the motor. The heaters
directly control what happens to the NC overload contacts in the
control circuit. When the heaters get hot enough, the overload
contacts open, and the M coil de-energizes. The loss of the
magnetic field allows spring pressure to open the three main
contacts in series with the motor, and the motor stops operating.
By de-energizing the one coil (M), all three sets of main
contacts open. Detrimental single phasing is avoided.
A minor disadvantage of the thermal overload device is its
need to cool off before being reset. Figure
16-12 shows a magnetic motor starter and the overload heater
and NC overload contact section separately.
The common thermal overload uses heater
coils in the main power line in series with the main contractors
and the motor stator windings. The current going to the motor
must go through the overload heaters first. These heater coils
surround a eutectic alloy solder pot (Figure
16-13). Eutectic means it has a very low melting point.
Characteristically, a eutectic solder goes from solid to liquid
and back again without developing a mushy condition.

The solidified solder holds a ratchet wheel
and pin assembly firmly in place (Figure
16-14). The ratchet wheel is under tension and holds a set of
contacts closed. These contacts have the ability to interrupt the
magnetic coil circuit that opens and closes the main contacts.
When the magnetic coil is de-energized, the main contacts open.
The main contacts no longer supply power to the motor, and the
motor stops (Figure 16-15).
The thermal overloads effectively monitor
motor current by developing a comparative heat in the heater
coils. The more current that flows though the heaters, the faster
the heaters become hot. When the motor is first started, the heat
from the momentary high inrush current is dissipated rapidly by
the heater coils. The operation of the motor is not interrupted.
If, however, the high current should last but another moment
longer, the contacts would open, and the motor would stop. If a
small overcurrent condition exists, the heaters will still get
hot enough to melt the eutectic alloy, but it will take longer.
Once enough heat is generated in the heaters and the eutectic
alloy melts, the ratchet wheel and pin assembly move under spring
pressure. As a result, the contacts in the control circuit of the
magnetic motor starter open. This de-energizes the coil in the
magnetic motor starter and opens the main contacts, disconnecting
the motor from the line. Notice in Figure
16-16 that the overload contacts are not in the motor power
supply line. They are in the control circuit that operates the
main contactors. The main contractors and the overload heaters
are in the motor's main three-phase supply line.

The protection afforded by the overload
device is determined by the heater coil selection. By using
different heater coils, a variety of overcurrent protection can
be selected. This must be based on the full-load current rating
of the motor. The temperature surrounding the motor and the
magnetic motor starter must also be considered. Heat and current
have the same destructive nature toward electrical equipment.
Electrical components in engine compartments are exposed to
greater heat than those in the ward room. Likewise, the
controller, which houses the magnetic motor starter, must be in
the same area as the motor it protects. Only in this manner will
the heater be affected by the same ambient temperature as the
motor windings.
Proper motor protection is required in the
motor control centers in the engine room. The MCC is air
conditioned, and the motors in the engine compartment are not. If
adequate motor protection selection is not provided, additional
investigation is necessary.
Every motor starter manufacturer has
specific overload guidelines supplied with the equipment.
Magnetic motor starters are provided with heater selection charts
because magnetic motor starters do not come with overload
heaters. Each heater must be identified for the specific motor
application, full-load current, and ambient temperatures. The
manufacturer guides are self-explanatory. Additional information
is available in the Code of Federal Regulations, Title 46,
Subpart 111.70, and the National
Electrical Code (NEC), Article 430.
A less common protective device is the magnetic overload relay
(Figure 16-17). This device uses a
current coil that creates a magnetic field in proportion to the
current carried in it. Once the magnetic field is strong enough,
the contacts are opened, and the circuit is de-energized. The
main benefit to this type of overload device is its ability to be
reset immediately.

Motors are designed and developed for
specific applications. Identifying their proper usage may be
difficult. To ensure the correct component for the correct
application, all government regulatory societies require a
minimum of specific information to be printed on the motor's
nameplate. Additional information may be obtained in IEEE Standard 45, Section 24, and (NEC) Article 430. This data includes --
-
- Manufacturer's name.
-
- Motor frequency. This may be represented as Hz for hertz
or as CPS for cycles per second. This is always an
indication of AC application.
-
- Phases (either three phase or single phase). This is also
an indication of AC application.
-
- Voltage. The motor is designed to operate at this voltage
or within a specified voltage range. Two voltages
separated by a slash, such as 450/225, indicate a
two-voltage system. Either voltage may be used by
connecting the electrical stator leads as directed in the
manufacturer's manual or on the data plate.
-
- Full-load current (FLC). This is the current required to
operate the motor at its rated load and speed. This is
not the current draw when the motor is started. If two
current values are given, this indicates the current when
supplied with one of the two possible voltage
connections. When the higher voltage is used, less
current is necessary to operate the motor.
-
- Full-load speed. This is the speed in revolutions per
minute the rotor will turn under full load.
-
- C rise. This Celsius value plus the motor's rated ambient
temperature add together to determine the maximum
temperature range the motor can obtain under full-rated
load (40C equals 104F).
-
- Time rating. This is the time the motor can operate
continuously without stopping. Usually 5, 15, 30, or 60
minutes or continuous ratings are specified.
-
- Rated horsepower.
-
- Code letter. This indicates the highest current the motor
will draw when the rotor is physically prevented from
moving initially. The current is rated in kVA per
horsepower. This is a measurement of locked rotor
amperage. Table 16-3 lists code
letters from the National Electrical Code.
-
- Design. This provides starting kVA, running kVA, and
running KW characteristics. This is a product of the
internal resistance of the rotor. Generally, designs B,
C, and D are used:
-- Design A is of limited usage. This motor has extremely
high starting kVA, as much as 50 percent higher than the
B, C, or D design motors. -- Design B is a standard
rotor design. This type of rotor has a low internal
resistance. It has normal starting torque, low starting
current, and low slip at full load.
-- Design C has a higher internal rotor resistance.
This improves the rotor power factor at the start,
providing more starting torque. Fully loaded, the extra
resistance creates a greater slip.
-- Design D has more resistance. The starting torque
is maximum.
-- Serial number. The serial number or identification
number is extremely useful when dealing with the
manufacturer. The serial number and appropriate
information is maintained on file with the company.
-- Type. This is the manufacturer's specific
application information. This will also identify the
housing characteristics (waterproof, drip-proof, and so
forth).
--Service factor. This is an allowable overload above
the full-load current. It is expressed as a decimal.
Multiplying the full-load current by the service factor
establishes the maximum allowable current acceptable
above full-load current for a short period of time.
-- Frame. Many of the dimensions found on a blueprint
are incorporated in the frame identification. Some of
these specifications may include the rotor shaft length,
diameter, and machining the motor housing and bolting
placements; and so forth.

When a motor is ordered, all the data plate
information must accompany the supply document. There is no
substitute for the correct electrical component. Universal
equipment does not exist in a marine distribution system unless
the specifications can be matched exactly.
Table 16-4 provides a sample of some
three-phase mot or starting characteristics for design B, C, or
D. Design A motors may have starting kVA values that are as much
as 50 percent higher. Many 3,600 RPM motors are design A.

Efficiency is the ratio of output to input.
Only part of the power going into a motor is actually delivered
to the load in the form of mechanical power. Some power is lost
in the resistance in the stator windings and in the stator core.
Other losses are transmitted across the air gap to the rotor.
Resistance in the rotor uses up power. Finally, the power needed
to overcome windage and friction losses reduces the mechanical
output even further.
The copper losses are proportional to the
current squared (P = I2R). This is the only variable
loss. Rotational and core losses do not change as the motor
becomes loaded.
HOMEPAGE